Our websites use cookies on your device to give you the best user experience. By using our websites, you agree to the placement of these cookies. To learn more, read our privacy policy.

Motion detector M48HC, DALI-2, master, High ceiling, 16-40  m, 360°, for surface mounting

General information

DALI Product ID5955
Product NameMotion detector M48HC, DALI-2, master, High ceiling, 16-40  m, 360°, for surface mounting
Brand NameNiko
StatusCertified: DALI-2
Product Part Number353-852411
GTIN5413736374256
Bus unit configuration-

Testing

Test conditionsPartial tests: Part 303, Part 304
Test typePartial
Family reference product ID5928
DALI test sequence software version2.3.2.0

Technical

Bus current consumption

Maximum current consumed from the bus power supply. If no value shown, 2mA is required.

0
Guaranteed supply current

Current that this bus power supply can provide. Total must be sufficient to provide the total "bus current consumption" of all devices.

200
Maximum supply current

Highest current that this bus power supply may provide. Total must not exceed 250mA.

250

Hardware/firmware information

If multiple versions exist then contact the manufacturer for details of the older versions.

Hardware version6.0, 7.1, 7.0, 37.11
Firmware version2.15, 2.18, 2.24, 2.26, 2.27, 2.30, 2.34

Product reference product description

DALI_2 P48

Description

This high ceiling detector is a DALI-2 master for DALI lighting control in up to 4 zones . The detector is fitted with multiple functions and can be controlled wirelessly using push buttons (360-21001). It is designed for surface mounting and has an IP54 protection degree. The lighting zones are defined during commissioning, using the Niko detector tool app and 2-way Bluetooth® communication between a smartphone and the detector.

DALI parts and versions

1012.0
1032.0
3032.1
3042.0

Product properties

This product can be used to update the firmware of other products that implement part 105 Firmware Transfer.

Sensors, switches, push-buttons, etc.

Maximum current consumed from the bus power supply. If no value shown, 2mA is required.

“Other properties” do not imply certification to such standards.



Reference design of firmware or hardware available